Operation Principle - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Name
Values (Range)
EventPriority11
EventPriority12
EventPriority13
EventPriority14
EventPriority15
EventPriority16
MaxEventPerSec
12.14.6

Operation principle

IED has an internal database of alarm events that are saved to non-volatile memory every 60
minutes. Alarms can be viewed only in the Web HMI.
An alarm event is generated by activating (0 to 1 transition) an INPUTx input, provided the input
number is included in the channel range specified by the EventChMask parameter.
When the BLOCK input is active, alarms are not generated. However, if an input is activated while
BLOCK is active and remains active when BLOCK is deactivated, an alarm event is generated with
the time stamp of the original input activation. Input pulses, that is, an activation followed by a
deactivation, while BLOCK is active, are ignored.
Alarm generation for an individual input is inhibited if the associated EventMask parameter is set to
NoEvents.
Each alarm event comprises the following information:
Technical Manual
Unit
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
Not defined
-
Note
Sensor Error
Warning
Alarm
Trip
3 - 30
Ev/s
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
Not defined
-
Not defined
-
Not defined
-
Not defined
-
Not defined
-
Not defined
1
15
Description
Priority of Event for input 11
Priority of Event for input 12
Priority of Event for input 13
Priority of Event for input 14
Priority of Event for input 15
Priority of Event for input 16
Max event per second
GUID-C3E2B54D-0D58-4F73-8E31-4EAA881DCD82 v1
Section 12
Monitoring
227