11.7.5

Settings

Table 149: MINMAX Non group settings (basic)
Name
Values (Range)
Operation
11.7.6

Monitored data

Table 150: MINMAX Monitored data
Name
MIN
INNO_MIN
MAX
INNO_MAX
11.7.7

Operation principle

MINMAX is used to determine the minimum and the maximum values out of the inputs. This function
is also used to identify the input channel number that has the minimum (MIN) and maximum (MAX)
value. If more than one input has the same value as the maximum, then the input channel number of
maximum value (INNO_MAX) provides the value with the lowest input channel number. Similarly, if
more than one input has the same value as the minimum, then the input channel number of minimum
value (INNO_MIN) provides the value with the lowest input channel number.
11.8
Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO
11.8.1

Identification

Function Description
Elapsed time integrator
11.8.2

Functionality

Elapsed Time Integrator (TEIGGIO) is a function that accumulates the elapsed time for which a
binary input signal has been high.
The main features of TEIGGIO are
Technical Manual
Unit
Off
-
On
Type
REAL
INTEGER
REAL
INTEGER
All channels should be connected to the functionality to work properly. This can be
achieved by connecting the last input signal to all the unused inputs of the function
block.
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
Off
Values (Range)
Unit
-
-
-
-
-
-
-
-
IEC 61850
IEC 60617
identification
identification
TEIGGIO
-
Description
Operation Off / On
PID-2824-MONITOREDDATA v1
Description
Minimum value of the inputs
Channel number having the minimum
value
Maximum value of the inputs
Channel number having the maximum
value
GUID-19AD4E73-DB73-4B1D-B0B3-78A9FB0FFE8E v1
GUID-DB37ECF3-9189-46A5-89BD-6FE39613EF7E v1
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v1
ANSI/IEEE C37.2 device
number
-
GUID-390D7433-0C1C-48B4-9A90-71AA148C3C35 v1.1.1
Section 11
Logic
PID-2824-SETTINGS v1
145