Section 12
Monitoring
transformer core type
electrical configuration and grounding (vector group) of the transformer
to which winding the load VT is connected
electrical configuration of the load VT
The required calculations for most common transformer configurations are described in the PWC600
User Manual and are implemented in the Switchsync Setting Tool (SST).
The resulting streams of limb voltage samples are published at the outputs LIMBU1, LIMBU2, and
LIMBU3. Internally, these limb voltages are normalized to p.u. using UBase setting (selected by
GlobalBaseSel), for calculating the residual fluxes in the next step.
Most power transformers have coupling between the phases, either through a delta winding
(electrical coupling) or through a three-limb core (magnetic coupling). Due to this inter-phase
coupling, energization of the first phase causes voltage to appear also in the other phase(s) although
the respective CB poles are still not closed. This makes it difficult to detect the actual making instant
in the later phase(s) to close. However, as the three voltages sum up to zero it is possible to detect
the later making instants from a suitable algebraic combination of limb voltages. In TRAFOSWT, the
TrafoType setting determines the appropriate combination as listed in
Table 287: Differential limb voltage signal outputs
Switch Case
1
2
3
4
5
6
7
8
9
The differential limb voltages are provided at the outputs DIFFLU1, DIFFLU2 and DIFFLU3. The
three-phase grouped signal for the same is the DIFFLU3P output.
324
Description
Differential voltage outputs
DIFFLU1
Yn, non-coupled
LIMBU1
Yn, coupled
(LIMBU1 - LIMBU2)/√3
Y, coupled/non-
LIMBU1
coupled
D, 30° (D1)
(LIMBU2 - LIMBU3)/√3
D, 330° (D11)
(LIMBU1 - LIMBU2)/√3
D, 210° (D7)
(LIMBU2 - LIMBU3)/√3
D, 150° (D5)
(LIMBU1 - LIMBU2)/√3
Z, 30° (Z1)
LIMBU1
Z, 330° (Z11)
LIMBU1
© 2021 Hitachi Energy. All rights reserved.
1MRK 511 557-UEN Rev. A
Table
287.
DIFFLU2
DIFFLU3
LIMBU2
LIMBU3
(LIMBU3 - LIMBU1)/
(LIMBU2 - LIMBU3)/
√3
√3
LIMBU2
LIMBU3
(LIMBU1 - LIMBU2)/
(LIMBU3 - LIMBU1)/
√3
√3
(LIMBU2 - LIMBU3)/
(LIMBU3 - LIMBU1)/
√3
√3
(LIMBU1 - LIMBU2)/
(LIMBU3 - LIMBU1)/
√3
√3
(LIMBU2 - LIMBU3)/
(LIMBU3 - LIMBU1)/
√3
√3
LIMBU3
LIMBU2
LIMBU2
LIMBU3
Technical Manual