Operation Principle - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Name
LOOPILX
INRUSHPLX
MECHHOLX
PPREARCLX
ADAPTCLLX
ADAPTOPLX
SCATTERLX
TMPOUT
12.18.7

Operation principle

The ACBMSCBR function is active whenever Operation is set to "On" and the BLOCKFUNC input is
0 (or unconnected).
Figure 119
described below.
Technical Manual
Type
Values (Range)
REAL
-
REAL
-
INTEGER
1=Ok
2=Warning
3=Alarm
REAL
-
REAL
-
REAL
-
REAL
-
REAL
-
displays the overall functionality of ACBMSCBR. The different sub-functions are
© 2021 Hitachi Energy. All rights reserved.
Unit
Description
A
Instantaneous current interrupted during
last open operation in this phase
A
Inrush current peak for this phase
-
Mechanical health indication based on
status of auxiliary contacts at conclusion
of CB operation
ms
Predicted pre-arcing time for closing of
this phase
ms
Adaptive correction offset for closing of
this phase
ms
Adaptive extension of target arcing time
for opening of this phase
ms
Switching target offset for handling
mechanical and electrical scatter in this
phase
deg
Temperature output
Section 12
Monitoring
GUID-B1ADD044-69A9-4959-BE1E-015707B7CEEF v2
273