Object Type; Function Switchover Blinds/Roller Blinds - ABB tacteo KNX Product Manual

Room outdoor sensor
Table of Contents

Advertisement

11.5.4.3

Object type

Options:
1 bit:
The value is sent as 1-bit switching commands (up/down or adjustment).
1 byte 0 - 100%:
The value is sent as 1-byte value without a sign (position in percent).
The parameter is used to set the size of communication objects for the control of blinds. For
selection "1 bit", objects "Sx: moving" and "Sx: adjusting" are available. For selection "1 byte 0-
100%", objects "Sx: position" and "Lx: slat position" are available.
If option "1 byte 0-100%" is selected, communication objects can be connected with 1-byte
position objects of the blind actuators. Also desired positions of the blind can be preset under
Extended parameters.
Example: Button 1 always moves the blind down to 50%, with the slats closed at 50%. Button 1
always moves the blind down to 80%, with the slats closed at 100%.
Note
The parameter can only be set if the "Blind/roller blind function switchover"
parameter is set on "Blind".
11.5.4.4

Function switchover blinds/roller blinds

Options:
Blind:
The application is fixed on blind control.
Roller blind:
The application is fixed on roller blind control.
The parameter is used to specify whether the sensor or the selected button can be used for a
blind or a roller blind control.
Note
If the "Blind" function is selected and parameter "Object type" is fixed on "1 byte
0-100%", the following parameters are available.
Product manual 2CKA001473B9488
Description of application and parameters
1 bit
1 byte 0 - 100%
Blind
Roller blind
Application "Function block x"
│70

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus knx