Duration Of Long Operation; Cycle Time Of The Telegram Repetition - ABB tacteo KNX Product Manual

Room outdoor sensor
Table of Contents

Advertisement

11.5.4.1

Duration of long operation

Options:
The application can differentiate between a short and a long press of the button. At a short
press of the button a telegram with the command "Move blind/rolller blind" is sent on the bus. At
a long press of the button a telegram with the command "Adjust slats" or "Stop roller blind" is
sent.
The parameter is used to specify the time after which a long button press is recognised. A
telegram is sent on the bus via communication object "Sx: adjust" or "Sx: stop" only after this
time has expired. A typical value for a long press of the button is 0.4 seconds.
Note
The command "Move blind" is sent immediately after the press of the button.
The command is also sent if the button is pressed long and a "Adjust slats"
command is sent due to the long operation. This causes a short jerking of the
blind since the first slats adjustment command is always interpreted by a blind
actuator as a stop command.
11.5.4.2

Cycle time of the telegram repetition

Options:
Telegrams are sent cyclic to the blind actuator via communication object "Sx: adjust" as long as
the button is pressed.
The parameter is used to set time intervals between the telegrams. The default setting is 1
second.
This function serves to more accurately position larger slats that require a longer time for a
complete slat rotation. This means that the button can remain pressed and be specifically
released when the slats have reached the desired position.
Note
The parameter can only be set if the "Object type" parameter is set on "1 bit" and
the "Blind/roller blind function switchover" parameter is set on "Blind".
Product manual 2CKA001473B9488
Description of application and parameters
Setting option from 00.300 to 03.000 (ss.fff)
Setting option from 00.100 to 05.000 (ss.fff)
Application "Function block x"
│69

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bus knx

Table of Contents