After bus voltage recovery the device is

Options:
Blocked:
The enable object has value"1" after bus voltage recovery.
Enabled:
The enable object has value "0" after bus voltage recovery.
The parameter serves to ensure that a defined behaviour is present on communication object
"EF: enable" after a return of bus voltage.
11.3.3.3

Use of automatic enable/blockage

Options:
No:
No automatic enable or blockage of the device.
Automatic enable:
Function "Automatic enable" is active.
Automatic blockage:
Function "Automatic blockage" ia active.
The parameter can be used to automatically enable or automatically block the device.
11.3.3.4

Automatic switchover time

Options:
The switching on or switchover always occurs immediately the user has approached the device.
The switching off or switchover can be delayed via the parameter. In this way, for example, the
display stays switched on for a while longer although the user has just moved away from the
device.
Note
This parameter can only be adjusted when the "Use of automatic
enable/blockage" parameter is set on "Automatic enable" or "Automatic
blockage".
Product manual 2CKA001473B9488
Description of application and parameters
Blocked
Enabled
No
Automatic enable
Automatic blockage
Setting option from 00:00:10 to 18:00:00 (hh:mm:ss)
Application "Device settings"