11.5.10.2

Light scene memory function

Options:
Deactivated:
A save command is not sent with the light scene call-up.
Activated:
A save command is sent with the light scene call-up with a long press of the button.
A memory bit can be sent in addition to the light scene number via the parameter.
A memory bit is set within the 1-byte value of the light scene number. If a light scene module
(e.g. Busch-ComfortTouch®) receives this 1-byte value, the module can identify the associated
light scene and trigger a storage process. Read requests are sent to all connected actuators
that answer with their current object values. The answers are saved by the light scene module
and are sent out at every new receipt of the light scene number.
11.5.10.3

Number of light scene

Options:
The parameter is used to specify the light scene number which is sent via the 1-byte
communication object "Sx: light scene number" at the press of the button.
The button serves exclusively as light scene extension unit, i.e. only the light scene number is
called up via the button. The individual values for the dimming actuators or blind actuators to be
adjusted are either stored in the actuator itself or in connected light scene modules (e.g. Busch-
ComfortTouch®). A light scene module receives the light scene number and subsequently
sends the stored light scene values consecutively to the connected actuators.