Setpoint Adjustment - Permanent Storage Of On-Site Operation - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

If this parameter is activated, a separate object can be used to delete the manual adjustment at
any time. Example of application: Resetting the manual adjustment on all devices located in an
office building using a system clock.
10.24.103
Setpoint adjustment — Permanent storage of on-site operation
Options:
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. The same applies to the operating mode.
If the device is re-programmed, the stored setpoint values will also be deleted.
Product manual 2CKA001473B5343
KNX control elements and application parameters
Activated
Deactivated
Activated
Application "Internal RTC"