Setpoint Settings; Setpoint Settings - Setpoint For Heating Comfort = Setpoint For Cooling Comfort; Setpoint Settings - Setpoint For Standby And Eco Are Absolute Values; Setpoint Settings - Hysteresis For Switchover Heating/Cooling - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

10.24.70 Setpoint settings

Note
The following parameters are available without enabling "Extended settings".
10.24.71 Setpoint settings — Setpoint for heating comfort = setpoint for cooling comfort
Options:
This parameter is used to configure the manner in which the setpoint adjustment functions.
Deactivated: The device has the same setpoint for heating and cooling in the comfort mode.
The system switches to heating mode when the temperature drops below the setpoint minus
hysteresis. It switches to cooling mode when the temperature exceeds the setpoint plus
hysteresis. The hysteresis can be parameterised.
Deactivated: The function has two separate setpoints for heating and cooling in the comfort
mode. The device will display the currently active setpoint value. Switching between heating
and cooling occurs via the "Switchover heating/cooling" parameter setting.
Notice
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".

10.24.72 Setpoint settings - Setpoint for standby and Eco are absolute values

Options:
The parameter is used to specify whether the setpoints for standby and Eco are absolute
values.

10.24.73 Setpoint settings - Hysteresis for switchover heating/cooling

Options:
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling mode. If
the room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating mode.
Notice
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
Product manual 2CKA001473B5343
KNX control elements and application parameters
Deactivated
Activated
Deactivated
Activated
Setting option between 0.5 - 10
Application "Internal RTC"
│256

Hide quick links:

Advertisement

Table of Contents
loading