Basic Stage Heating - Cyclic Sending Of The Control Value; Additional Stage Heating - Pwm Cycle Heating; Basic Stage Heating - Maximum Control Value (0 - 255); Basic Stage Heating - Minimum Control Value For Basic Load (0 To 255) - ABB SmartTouch B/stainless Product Manual

Table of Contents

Advertisement

Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".
10.24.13 Basic stage heating — Cyclic sending of the control value
Options:
The current control value used by the device can be cyclically transmitted to the bus.
Notice
This parameter is only available when the "Control value type" parameter is
set either on "2-point 1 Bit, Off/On, 2-point 1 Byte, 0/100%", "PI continuous, 0-
100%" or "Fan coil".

10.24.14 Additional stage heating - PWM cycle heating

Options:
In PI PWM, On/off the control value percentage values are converted into a pulse-interval
signal. This means that a selected PWM cycle will be divided into an on-phase and an off-phase
based on the control value. Accordingly, a control value output of 33% in a PWM cycle of 15
min. results in an On-phase of five minutes and an Off-phase of 10 min. The time for a PWM
cycle can be specified here.
Notice
This parameter is only available when the "Control value type" parameter is set
on "PI PWM, On/Off".
10.24.15 Basic stage heating — Maximum control value (0 - 255)
Options:
The maximum control value of the PI controller defines the maximum value outputted by the
controller. If a maximum value under 255 is chosen, the value will not be exceeded, even if the
controller calculates a higher control value.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".
10.24.16 Basic stage heating — Minimum control value for basic load (0 to 255)
Options:
The minimum control value of the PI controller defines the minimum value output by the
controller. If a minimum value greater than zero is chosen, the controller will not output a lower
value, even if it calculates a value that is lower. This parameter can be used to set a basic load,
e.g. for operating floor heating. Even if the controller calculates the control value zero, a heating
Product manual 2CKA001473B5343
KNX control elements and application parameters
00:01:00 - 01:00:00
00:01:00 - 01:00:00
Setting option between 0 - 255
Setting option between 0 - 255
Application "Internal RTC"