ABB SmartTouch B/stainless Product Manual page 226

Table of Contents

Advertisement

Text x for value [0 - 255]:
Options:
Setting options from 0 - 255
The parameter is used to set which value is to be converted into text x.
Text x:
Options:
<Text>
Naming of the value. The length of the text is limited to 15 characters.
1 byte -> 8x1 bit: A 1-byte value is converted into eight 1-bit values. The following
parameter appears:
Sending output values:
Options:
At every receipt
At changed values
The parameter is used to specify when the 1-byte value is converted and sent.
2 byte -> 16x1 bit: A 1-byte value is converted into sixteen 1-bit values. The following
parameter appears:
Sending output values:
Options:
At every receipt
At changed values
The parameter is used to specify when the 1-byte value is converted and sent.
Time function: The 1-bit communication objects "Input" and "Output" are available for the
time function.
When an ON telegram is received via 1-bit communication object "Input", the staircase light
period is triggered and an ON telegram is sent on the 1-bit communication object "Output".
After the set period has expired, an OFF telegram is sent via the output object.
If an OFF telegram is received during the staircase light period, the staircase light period is
reset and an OFF telegram is sent on the output.
If an ON telegram is received again during the staircase light period, the delay time can be
restarted again (retrigger). If this behaviour is desired, the "Retrigger" parameter is to be set
on "Yes". A switch-on delay time can be additionally activated. This means that the start of
the staircase light period and the sending of an ON telegram on the output object can
happen only after the switch-on delay time has expired.
The following parameters are displayed:
Type of time function:
Options:
The parameter is used to select between a staircase light function and an On/Off delay.
Staircase lighting: The following parameters are displayed:
Staircase light period [hh:mm:ss]:
Options:
The time of the switch-off delay (hh:mm:ss) is set via the parameter.
Use of switch-on delay time:
Product manual 2CKA001473B5343
KNX control elements and application parameters
Staircase lighting
ON/OFF delay
Setting options from 00:00:01 - 12:00:00
Application "Logical functions"
│226

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents