7.3.4 Physical Ports

Table 7-12
Table 7-12 Physical port description
Item
Refrigerant liquid pipe
Refrigerant gas pipe
Humidifier water inlet
pipe
Top drainpipe
Bottom drainpipe

7.3.5 Technical Specifications

Table 7-13
NetCol5000-A in-row smart cooling product.
Table 7-13 General specifications
Item
Cooling mode
Refrigerant
Cooling capacity
Air volume
Air supply mode
Certification
Cooling capacity test conditions: dry bulb temperature at air return vent: 37° C; relative
Issue 06 (2020-05-21)
The controller provides abundant external ports such as RS485 ports, CAN ports, FE
ports, and USB ports that are protected by a security mechanism.
The smart cooling product supports communications protocols such as Modbus RTU,
Modbus TCP, and SNMP, facilitating connection to the network management system.
The controller intelligently identifies abnormal parameter settings (incorrect commands)
and rejects them automatically.
If the indoor temperature fluctuates beyond the normal range, an audible and visible
alarm signal is sent automatically.
shows the physical ports on the NetCol5000-A in-row smart cooling product.
and
Table 7-14
respectively show the main technical specifications of the
Copyright © Huawei Technologies Co., Ltd.
Specifications
Copper pipe; outer diameter: 5/8 in.; pressure resistance ≥ 4.5
MPa; welded
Copper pipe; outer diameter: 3/4 in.; pressure resistance ≥ 4.5
MPa; welded
Reserved port: BSPP 1/2 in.; thread connection
Reserved port: BSPP 1/2 in.; thread connection
Reserved port: copper pipe with an outer diameter of 5/8 in.;
you are advised to use a hose with an inner diameter of 14 mm
for connection.
Specifications
Air cooled
R410A
35 kW
3
6000 m
/h
Horizontal air supply
REACH, RoHS, CE, WEEE, China Energy Conservation
Certification, and IEC
7 Temperature Control System
115