Huawei FusionModule2000 Product Description page 59

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Silk
Screen
0V
GEN
0V
BCB_OL
BCB_STA Port for monitoring the
BCB_DR
V
BCB_0V
EPO_NO
EPO_12V
EPO_NC
EPO_12V
SWITCH
STATUS_
OUT
SWITCH
STATUS_
0V
SWITCH
STATUS_
MT
SWITCH
Issue 06 (2020-05-21)
Description
grounding faults
Port for signal ground
Port for detecting diesel
generator (D.G.) mode
Port for signal ground
Port for detecting the BCB
box
battery switch
Controls battery circuit
breaker trip. When the
voltage is +12 V, the circuit
breaker trips.
Port for signal ground
Emergency power-off
(EPO) port
+12 V
EPO port
+12 V
Port for monitoring the UPS
output circuit breaker
Port for signal ground
Port for monitoring the
maintenance circuit breaker
Port for signal ground
Copyright © Huawei Technologies Co., Ltd.
5 Power Supply and Distribution System
Status
grounding fault
Disconnected: no
battery grounding
fault
Connected: D.G.
mode
Disconnected:
non-D.G. mode
Grounded: BCB
box connected
Disconnected:
BCB box not
connected
Connected: battery
switch ON
Disconnected:
battery switch
OFF
0 V: battery
switch not tripped
12 V: battery
switch tripped
If the normally open
(NO) port is
connected to the
EPO_12V port, EPO
is triggered.
If the normally closed
(NC) port is
disconnected from the
EPO_12V port, EPO
is triggered.
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Disconnected:
circuit breaker ON
Connected: circuit
breaker OFF
Initial Status
Disconnected
Grounded
Disconnected
0 V
Disconnected
Connected
Connected
Disconnected
51

Advertisement

Table of Contents
loading

Table of Contents