Huawei FusionModule2000 Product Description page 180

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Figure 8-29 Multi-functional sensor
(1) Address DIP switch
(4) RF_Z indicator
Specifications
Table 8-38 Multi-functional sensor technical specifications
Item
Temperature
monitoring
Humidity
monitoring
Smoke
monitoring
POE port
RS485 port
DI input
BLINK button
Test button
Issue 06 (2020-05-21)
(2) BLINK button
(5) RUN indicator
Specifications
–40°C to 70°C. Precision ≤ ±0.5 °C (0-50 ° C).
0 to 100% RH. Precision ≤ ±5% RH (25°C, 20%–80% RH).
Complies with Ul217. The smoke sensor generates an alarm when
testing 3.2% weak dust for each foot.
One POE port that complies with IEEE802.3 at.
Reserves one RS485 port.
One DI input port, 12 V DC power input.
Wireless communication:
If the sensor is not connected to the network, after you hold down
the button for 2s to 3s, the sensor connects to the network in RF_Z
mode.
If the sensor is connected to network, after you hold down the button
for 2s to 3s, the RUN indicator blinks.
Hold down the button for more than 6s to clear network parameters.
Supports the smoke sensor test.
Copyright © Huawei Technologies Co., Ltd.
8 Intelligent Module Management System
(3) TEST button
(6) ALM indicator