Huawei FusionModule2000 Product Description page 170

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Specifications
Table 8-26 Technical specifications for a smart ETH gateway
Item
Power input
Power output
FE port
POE port
BLINK
button
Indicators
Table 8-27 Indicators on a smart ETH gateway
Indicator
PWR
RUN
Issue 06 (2020-05-21)
Specifications
PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output voltage
range: 45–55 V DC
Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
Four POE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
If you press the BLINK button, the RUN indicator blinks intermittently at
super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.
Color
Name
Green
Power input
status indicator
Green
Module
running status
indicator
Copyright © Huawei Technologies Co., Ltd.
8 Intelligent Module Management System
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power supply is
abnormal.
Blinking at
The smart ETH gateway
long
successfully registers with
intervals
the ECC800-Pro and the
software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
The smart ETH gateway does
short
not register with the
intervals
ECC800-Pro (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
162

Advertisement

Table of Contents
loading

Table of Contents