Monitoring Interface Card - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Silk
Screen
EPO_NC
EPO_12V
SWITCH
STATUS_
OUT
SWITCH
STATUS_
0V
SWITCH
STATUS_
MT
SWITCH
STATUS_
0V
SWITCH
STATUS_
BP
SWITCH
STATUS_
0V
SPD
0V

5.2.1.4.4 Monitoring Interface Card

Issue 06 (2020-05-21)
Description
EPO port
+12 V
Port for monitoring the UPS
output circuit breaker
Port for signal ground
Port for monitoring the
maintenance circuit breaker
Port for signal ground
Port for monitoring the
bypass input circuit breaker
Port for signal ground
Port for monitoring the
input AC surge protective
device (SPD)
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
Copyright © Huawei Technologies Co., Ltd.
5 Power Supply and Distribution System
Status
If the normally closed
(NC) port is
disconnected from the
EPO_12V port, EPO
is triggered.
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Disconnected:
circuit breaker ON
Connected: circuit
breaker OFF
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected: SPD
enabled
Disconnected:
SPD disabled
2
2
to 1.5 mm
.
Initial Status
Connected
Connected
Disconnected
Connected
Connected
34