FusionModule2000 Smart Modular Data Center
Product Description
Table 5-47 Technical specifications
Item
Rated operating voltage
Rated frequency
Rated operating current
Input switch
Output switch
IP rating
Surge protection level
Certification
Installation mode
Flame spread rating

5.2.7 Battery Cabinet

A maximum of two battery groups and up to four battery cabinets (in 2N scenario) can be
deployed inside the smart module. If many batteries are configured, they can be deployed
outside the smart module.
The battery cabinets provide space for installation and cabling of batteries and the iBattery
intelligent battery management system for the smart module.
Issue 06 (2020-05-21)
If the configured batteries can be placed in four or fewer battery cabinets, it is
recommended that battery cabinets be deployed inside the smart module (smart module
A). Battery cabinets or racks can also be deployed with UPS batteries outside smart
module A (batteries deployed outside) or smart module B.
If the number of configured batteries exceeds the capacity of four battery cabinets, it is
recommended that battery racks be deployed outside smart module A (batteries deployed
outside) or the smart module B. Battery cabinets can also be deployed with UPS batteries
outside smart module A (batteries deployed outside) or smart module B.
Copyright © Huawei Technologies Co., Ltd.
Technical Specifications
380 V/400 V/415 V
50/60 Hz
250 A/400 A
250 A/3P MCCB, 400 A/3P MCCB
Rated current 250 A/400 A: 8 x 63 A/3P + 2 x 10 A/1P + 1 x
32 A/1P MCB
IP20
Level C SPD
CE, CCC
Wall-mounted
Fire-retardant materials with a flame spread rating of V0 are
used. The heat shrink tubing is at least 1 mm thick.