Water Quality Requirements for Electrode Humidifiers
If the inlet water contains large granules, install a water filtering device at the inlet port to
prevent pipe blockage.
The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve must be
installed if the inlet water pressure exceeds 0.7 MPa.), and the temperature should be in the
range of 1° C–40° C.
Table 7-7 Water quality requirements for electrode humidifiers
Item
Hydrogen ion
Conductivity at 20° C
Inlet water hardness
specifications
a: When σ
long; when σ
b: A water softener needs to be installed if the inlet water hardness exceeds 100 mg/L
(CaCO

7.2.4 Technical Specifications

Table 7-8
Table 7-8 General specifications
Item
Cooling mode
Refrigerant
Air flow mode
Dimensions (H x W x D)
Net weight
Issue 06 (2020-05-21)
a
)
20
b
is less than 125 µ S/cm, the first vapor exhausting duration of the humidifier is
20
greater than 1250 µ S/cm, the humidifier service life is affected.
20
).
3
and
Table 7-9
describe the general and optional specifications of the NetCol5000-A.
Copyright © Huawei Technologies Co., Ltd.
Requirement
7–8.5
125–1250
≤ 100
Specifications
Air cooled
R410A
Horizontal air flow
2000 mm x 300 mm x 1100 mm (cabinet)
2000 mm x 300 mm x 1200 mm (cabinet with an
enclosure frame)
2200 mm x 300 mm x 1100 mm (cabinet with an
enclosure frame, customizable)
2200 mm x 300 mm x 1200 mm (cabinet with top and
enclosure frames)
230 kg
7 Temperature Control System
Unit
pH
µ S/cm
mg/L
107