General Input Unit - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Table 5-44 Monitoring specifications
Item
Power distribution mains input
Power distribution branch output

5.2.5.1 General Input Unit

The general input unit is classified into two types: left-installed general input unit and
right-installed general input unit.
Figure 5-54 General input unit
(1) Alarm indicator
(5) PWR_1 port
(9) SPD circuit
breaker
Issue 06 (2020-05-21)
When the personnel are close to the cable tray and face the aisle, the left cabinets use the
left-installed general input unit, and the right cabinets use the right-installed general
input unit.
Left-installed general input unit: Cables are routed in from the right and out from the left.
Right-installed general input unit: Cables are routed in from the left and out from the
right.
(2) Monitoring
panel
(6) FE port
(10) Cable inlet
Copyright © Huawei Technologies Co., Ltd.
5 Power Supply and Distribution System
Specifications
Detects the voltage, current, active power,
reactive power, power factor, electric
energy, harmonic, and key node
temperature.
Detects the branch loop current, load
percentage, active power, apparent power,
electric energy, and key node temperature.
(3) Integrated management
card
(7) SPD
(11) Cable outlet
(4) PWR_2
port
(8) Input
switch
69