Huawei FusionModule2000 Product Description page 68

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Table 5-33 Mains Input electrical specifications
Item
Input system
Rated input voltage
Input voltage range
Input frequency range
Rated frequency
Input power factor
THDi
Table 5-34 Bypass Input electrical specifications
Item
Input system
Rated input voltage
Input frequency range
Table 5-35 Battery specifications
Item
Battery voltage
Issue 06 (2020-05-21)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
30–40° C environment: not derated when the voltage is
187–280 V; linearly derated to 40% load when the voltage
is 187–80 V
0–30° C environment: not derated when the voltage is
176–280 V; linearly derated to 40% load when the voltage
is 176–80 V.
40–70 Hz
50/60Hz
> 0.99 (full load); > 0.98 (half load)
≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear load;
maximum: 5%)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz ± 6 Hz (adjustable with the tolerance of 0.5–6 Hz, ± 2
Hz by default)
Specifications
360–528 V DC
12 V battery: 30–44 batteries, 40 batteries by default; not
derated when there are 36–46 batteries; power derated to
94% when there are 34 batteries; power derated to 80%
when there are 32 or 30 batteries.
2 V battery: 180–264 batteries, 240 batteries by default;
not derated when there are 16–276 batteries, power
derated to 0.94 when there are 204–214 batteries; power
derated to 0.8 when there are 180–212 batteries. The
number of batteries in the positive battery string must be
Copyright © Huawei Technologies Co., Ltd.
5 Power Supply and Distribution System