7.2.3 Application Environment

Do not install the smart cooling product near a noise-sensitive place such as an office or a
conference room.
Table 7-3–Table 7-7
requirements, and water quality requirements of the NetCol5000-A.
Environmental Specifications
Table 7-3 Environmental specifications
Item
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Outdoor temperature
Protection level
Issue 06 (2020-05-21)
The controller controls the indoor temperature precisely and responds quickly.
The controller is protected by a multi-level password protection mechanism, avoiding
misoperations.
Password verification is required upon the first startup to ensure the system security. No
password verification is required for subsequent startup if the first verification succeeds.
The display panel displays the operating status and duration of the smart cooling product
components in real time.
The fault diagnosis system automatically displays the information about current faults,
which facilitates the maintenance.
The controller provides a variety of external ports including a fast Ethernet (FE) port and
universal serial bus (USB) port that is protected by a security mechanism.
describe the operating environment, physical ports, installation
Copyright © Huawei Technologies Co., Ltd.
Specifications
18–45° C
20%–80% RH
–40° C to +70° C
5%–95% RH (non–condensing)
Working with the NetCol500–A032 (including
low–temperature components): –40° C to +45° C
Working with the NetCol500–A036 (including
low–temperature components): –40° C to +55° C
Working with the NetCol500–A036: –20° C to +55° C
Working with the NetCol500-A026SC11E0: –20° C to
+45° C
Working with the NetCol500-A0265S11E0: –20° C to
+55° C
Working with the NetCol500-A0265S11E0 (including
low–temperature components): –40° C to +45° C
Indoor unit: IP20
Outdoor unit: IPX5