Ac Actuator - Huawei FusionModule2000 Product Description

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description

8.3.10.1 AC Actuator

The AC actuator is used in a smart module to control the lighting inside the smart module by
receiving commands from the access control system or host, infrared linkage information
(disabled by default), or signals from the light button. It also provides a charging port for the
pad.
Figure 8-44 AC actuator
(1) AC OUT2 port
(5) BLINK button
Specifications
Table 8-58 AC actuator technical specifications
Item
Power input
Power output
Wireless
Issue 06 (2020-05-21)
(2) AC OUT1 port
(6) AI/DI dry
contact
Specifications
One AC input, 100–240 V AC.
AC OUT1: two AC outputs, 100–240 V AC, maximum total
current: 5 A.
AC OUT2: one AC output, 100–240 V AC, maximum
current: 5 A.
One wireless communication port, complying with
Copyright © Huawei Technologies Co., Ltd.
8 Intelligent Module Management System
(3) AC IN port
(7) COM1–2 RS485
port
(4) Status indicator