5.10.2
Installing IP42 roof-mounted cooling units
One by one, install the IP42 roof-mounted cooling units on top of the PCU
compartments that have the designated openings.
Item
Self-tapping Torx screws
Washers with sealing
Cable binders
1. Align the unit with the opening (1) in the cabinet roof.
2. Slowly lower the cooling unit onto the cabinet roof.
IMPORTANT! Make sure that the screw holes fit.
3. Screw the cooling unit to the cabinet roof.
4. To get to the cable inside the cabinet, remove the back wall if
necessary to reach them from the back.
3BHS799208 E01 REV E
Table 5-2 Installation material per IP42 unit
Quantity
18
18
ACS5000 WATER-COOLED USER MANUAL
05 MECHANICAL INSTALLATION
Details
M6x16
6.8x1 (4.8x2.8)
1
80/186