ABB ACS5000 User Manual page 131

Water-cooled
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

If a fault cannot be reset, it must be rectified by the
responsible personnel.
When no alarms and faults are present and the drive is ready, the CDP
control panel displays ReadyOn.
4. Press the SUPPLY ON pushbutton on the control compartment door
to charge the DC link. The pushbutton flashes during charging.
The status line of the CDP control panel alternates between Charging
and AuxiliaryOn.
1 L ->
StateINU
MOTOR SP
POWER
After charging has been finished, the following takes place:
• The main circuit breaker closes automatically.
• The SUPPLY ON pushbutton lights up permanently.
5. Enter the reference value.
Note: For more information, see "9.3.2 Entering a reference value"
on page 159.
3BHS799208 E01 REV E
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP
0.00 rpm
POWER
0.0 kW
0.0 rpm
Charging
0.00 rpm
0.0 kW
1 L ->
0.0 rpm
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
1 L ->
[600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP
0.00 rpm
POWER
0.0 kW
ACS5000 WATER-COOLED USER MANUAL
Alternating display message:
• Charging
• AuxiliaryOn
0
08 OPERATION
131/186