3.14.6 Teamwork Networking and Monitoring

Context
Teamwork communication ports "J73UP" and "J73DOWN" on the side panel of the electric
control box are used to enable CAN teamwork networking and RS485 monitoring.
Figure 3-47 Ports on the two main control boards
(1) J73DOWN
(3) DIP switch
Issue 09 (2020-01-10)
Name
No. 1
Hot aisle 1
OFF
T/H
Hot aisle 1
ON
T/H
The default state of RS485_R is OFF, and there is no need to operate it.
After the addresses are set, choose Settings > System Settings > T/H Sensor on the controller home
screen and set the sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
The NetCol5000-C with main control board 1 uses the software of V100R001, and NetCol5000-C with
main control board 2 uses the software of V100R002.
Copyright © Huawei Technologies Co., Ltd.
No. 2
No. 3
No. 4
ON
ON
OFF
ON
ON
OFF
(2) J73UP
3 Installation
No. 5
No. 6
ON
OFF
ON
OFF