Figure 3-15 Checking the pressure
----End
Follow-up Procedure
Check that thermal insulation foam is in close contact with the pipes, there is no crack in each
cutting position, and the chilled water valve is tightly wrapped by thermal insulation foam.

3.5 Installing Water Pipe Adapters

Context
As illustrated in
outlet pipes to reserved ports in the cabinet. Accordingly there are three methods to install
water pipe adapters. If the NetCol520 is deployed, use method A shown in
Issue 09 (2020-01-10)
Before opening the exhaust valve, open the chilled water valve to the maximum scale. For details about
how to open the chilled water valve, see
If gas emits, the system is normal. Slowly open the exhaust valve to discharge nitrogen
and close the valve when there is no airflow through the valve.
If no gas emits out of the valve, contact Huawei technical support.
Table 3-5
and
Copyright © Huawei Technologies Co., Ltd.
Step 1
in
3.12 Leakage Test with
Figure
3-9, there are three methods to connect water inlet or
3 Installation
Nitrogen.
Figure 3-9
to
43