Huawei NetCol5000-C Series User Manual page 103

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Step 2 Set teamwork control parameters.
You can set all the teamwork control parameters on the master smart cooling product but only
Teamwork group no., Teamwork unit address, and Teamwork function on a slave smart
cooling product, and other parameters of the slave smart cooling products will be modified by
the master smart cooling product synchronously.
parameters.
Table 4-6 Teamwork settings
Parameter
Teamwork group
no.
Teamwork unit
address
Teamwork
function
Teamwork mode
Network
Total number of
units
Number of
running units
Issue 09 (2020-01-10)
Description
The number of the
teamwork controlled
group, which is the
same for all the devices
in the group.
Only one device in each
group can be set to 1.
Other device addresses
should be different from
each other.
Disable or enable the
teamwork function. If
the teamwork function
is disabled, this device
is operating according
to its own control. If the
teamwork function is
enabled, this device
works in harmony with
others that in the same
group.
Set the teamwork mode.
The options include
Smart and iCooling.
Networking mode for
the teamwork.
Number of the smart
cooling products in this
group (1 to 32 can be
set).
Number of running
units in a group. The
Copyright © Huawei Technologies Co., Ltd.
Table 4-6
describes how to set the
Configuration
Principle
Set the assigned
teamwork control
number.
Set the assigned unit
address.
Set this parameter
based on the onsite
device heat
distribution.
Determine whether to
enable the iCooling
mode based on onsite
heat load variations. If
the heat load varies
greatly, it is
recommended that
you enable the
iCooling mode.
Networked over CAN.
Total number of the
smart cooling
products in this group.
The master unit
assigns the devices to
4 ACC Introduction
Default Value
1
NA
Disable
Smart
CAN
3
2
94