Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
When connecting the rubber hose, ensure that the pipe is not excessively bent and does not have a
secondary trap, and the hose gradient is 1:100.
1.
2.
3.
4.
5.
Issue 09 (2020-01-10)
Remove the clamp and take off the rubber hose reserved on the equipment, as shown by
(1) in
Figure
3-29.
Figure 3-29 Connecting a rubber hose
Install the DN19 rubber hose at the pagoda connector, as shown by (2) in
Determine the hose length based on site requirements.
Tighten the hose clamp to a torque of 4 N· m.
Connect the automatic condensate drainpipe to the condensate drainage port in the
equipment room.
Fully wrap the drainpipe with thermal insulation foam.
Connecting a PPR or aluminum plastic pipe
a.
Remove the plug, as shown by (1) in
Figure 3-30 Connecting a PPR or aluminum plastic pipe
Copyright © Huawei Technologies Co., Ltd.
Figure
3-30.
3 Installation
Figure
3-29.