NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Procedure
Step 1 (Optional) Turn the power selection switch to the position with the same line voltage as the
mains using a flat-head screwdriver.
Figure 3-40 Turning the power selection switch
Step 2 Take M4 OT terminals from the fitting bag and crimp the OT terminals and cables using a
crimping tool, as shown in
terminal.
Figure 3-41 OT terminal
(A) Cable core
Issue 09 (2020-01-10)
This step applies to NetCol5000-C030H7.
Crimp the cables firmly and ensure that they are not loose after pulling.
If the cables do not meet the recommended specifications, you need to prepare terminals
by yourself.
Copyright © Huawei Technologies Co., Ltd.
Figure
3-41.
Figure 3-42
(B) Cable
shows how to prepare a cord end
(C) OT terminal
3 Installation
68