Huawei NetCol5000-C Series User Manual page 85

Simple configuration in-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
Figure 3-53 Y-split cable connection for teamwork control
(Optional) Setting the DIP Switch on the Main Control Board
This step is only for the NetCol5000-C with main control board 1.
Table 3-8 Operation of the switches on the main control board
Switch
1
2
3
4
5
6
7
8
Issue 09 (2020-01-10)
Figure 3-53
shows the scenario where every two smart cooling products connect to the EMS over a
Y-split cable. Determine the positions of Y-split cables based on performance requirements.
When the EMS monitors smart cooling products using the RS485 protocol, the time needed for
collecting all data from a single smart cooling product is 3 seconds. In the teamwork mode of
cascading using an RS485 bus for monitoring, it takes the EMS 3 seconds multiplied by N to collect
data from N smart cooling products in the group. For example, the time needed for collecting data
from four smart cooling products is 12 seconds. If the EMS needs longer time to collect data from
all smart cooling products than what the EMS performance requires, use the Y-split cable connection
scheme shown in
Figure
Default
Value
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Copyright © Huawei Technologies Co., Ltd.
3-53.
Description
Remaining in OFF.
Remaining in OFF.
Remaining in ON.
Remaining in ON.
Remaining in OFF.
Remaining in ON.
When teamwork mode is not deployed, remain in OFF.
When teamwork mode is deployed, toggle switches on the
main control boards of the first and last units to ON and
other remains in OFF.
Remaining in ON.
3 Installation
76