NetCol5000-C030 In-row Chilled Water Smart Cooling
Product
User Manual (Simple Configuration)
4.5.11 Rectifying Faults of the E-label Identification Board
Context
If strong electromagnetic interference exists, the E-label identification board is abnormal, or
the E-label identification board is not properly connected, an exception may occur during
E-label identification.
Figure 4-55 Message 1
Figure 4-56 Message 2
Procedure
Step 1 Check whether strong electromagnetic interference exists around the E-label identification
board.
Issue 09 (2020-01-10)
If the information shown in
cooling product can run properly. To remove this tip, perform
If the information shown in
cooling product cannot run properly. Perform
In the
Figure 4-56
the ACC V100R001C20SPC300 version is used as an example to describe the prompt
messages on the screen. During actual operations, the version in use prevails.
Copyright © Huawei Technologies Co., Ltd.
Figure 4-55
is displayed on the controller LCD, the smart
Figure 4-56
is displayed on the controller LCD, the smart
Step 2
4 ACC Introduction
Step
1.
to end.
128