4.3.2.2 Start and Shutdown

Context
Tap the Start or Shutdown buttons on the home screen to start or shut down the smart
cooling product.
Procedure
Step 1 Tap Start or Shutdown on the home screen. A warning is displayed, indicating whether to
start or shut down the smart cooling product, as shown in
successfully started or shut, the system displays a message, indicating that the command is
successfully triggered.
Figure 4-5 Start and shutdown
----End

4.3.2.3 Setting Temperature and Humidity Values

Context
Log in as the Admin or Engineer user to perform the following operations:
Issue 09 (2020-01-10)
If a power failure occurs and the smart cooling product is powered on again, the smart cooling
product automatically restores to the original state (start or shutdown) before the power failure.
The hardware port for controlling the status of the remote dry contact or On/Off status on remote is
reserved on the ACC. The status of the remote dry contact and On/Off status on remote is on by
default.
The operations that start the smart cooling product successfully by the LCD button or by element
management system (EMS) is effective only when the remote dry contact or On/Off status on remote
is on the status of on.
In start mode, the Start button is green (unavailable) and the Shutdown button is gray (available).
In shutdown mode, the Shutdown button is green (unavailable) and the Start button is gray
(available).
Set T/H control type.
Set Temp control mode.
Set cold aisle sensors 1, 2, and 3, and hot aisle sensors 1, 2, and 3.