Ensure that the holes intended for combining cabinets on the smart cooling product are
aligned with those on an adjacent IT cabinet.
Do not remove anchor bolts. Otherwise, you need to rework them for use.
Adjust the anchor bolts by performing the following operations:
Comply with the following requirements to level and combine cabinets:
3.
Issue 09 (2020-01-10)
Drill holes into the floor at the smart cooling product installation position based on site
requirements. For hole specifications, see
Measure the smart cooling product height using a measuring tape and level, and level the
smart cooling product by adjusting the anchor bolts under it using a wrench.
Figure 3-21 Leveling the smart cooling product
Adjust the anchor bolts using a wrench to adjust the cabinet height.
Adjust the four anchor bolts flexibly based on the height and levelness.
Level the cabinet with the help of a measuring tape. Check that the vertical distance between the top
of the cabinet and the floor is 2000 mm (tolerance ± 2 mm) and that the cabinet is leveled
horizontally.
Wrench an anchor bolt clockwise to elevate a cabinet leg, or wrench an anchor bolt anticlockwise to
lower it. A cabinet leg can be adjusted within a range of 0–8 mm.
Install the air baffle by using four M10 bolts available in the accessories. The required
torque is 30 N· m.