(2) Output specifications
Analog output
Signal name
voltage/current
Servo ON signal (SVON)
Speed command signal
0 to ±10VDC/10mA
(analog signal)
*1
The load current of Servo ON signal (SVON) is 30mA at the maximum. When using a miniature relay, take the load
current into consideration.
Load
Output method
voltage
4.75 to
Open collector
26.4VDC
CHAPTER 3 SPECIFICATIONS
Max.
Load
voltage
current
drop at
current at OFF
ON
1.0V or
*1
0.1mA or lower
Max.30mA
lower
Leakage
3