6.2.6

Encoder I/F setting

Select an encoder output type from open collector, TTL, or differential output.
For connection between the QD73A1 and an encoder, refer to the following.
Page 66, Section 4.6.2
6.2.7

Analog voltage resolution setting

Set resolution of analog voltage to be output as a speed command.
The default value of "Analog voltage resolution setting" is "12-bit resolution". When the analog voltage resolution of the
connected drive unit is higher than 12 bits and the motor rotates even with a tiny voltage, the resolution can be set higher (14
bits or 16 bits). In that way, fine control can be achieved.
CHAPTER 6 VARIOUS SETTINGS