iBattery 3.0
User Manual
Figure 5-16 Settings page
Step 5 Click Connection Test and save the setting after a message indicating successful connection
appears.
----End

5.5 Networking the iBOX and iBAT

Context
Parameters have been set depending on the preceding scenarios.
If the UPS does not charge batteries for a long time, power off the iBOXs to prevent damage
to batteries. After an iBOX has powered off for 30 minutes, the iBATs automatically
hibernate.
An iBAT hibernates automatically under the following conditions:
Issue 07 (2019-12-30)
Keep IP Address consistent with the iBOX IP address and set the port to 502.
If ModbusTCP encryption and ModbusTCP authentication on the iBOX WebUI are set to
Disable, select Non-SSL Connection for Connection Mode. If ModbusTCP encryption and
ModbusTCP authentication are set to Enable, select SSL Connection for Connection Mode.
When multiple iBOXs are connected in parallel, you need to set parameters on the NetEco for each
iBOX.
The iBAT has failed to communicate with the iBOX for more than 30 minutes.
The iBAT has not been networked successfully more than two days after power-on.