Setting Parameters For The Scenario Where The Ibox Connects To The Neteco - Huawei iBattery 3.0 User Manual

Hide thumbs Also See for iBattery 3.0:
Table of Contents

Advertisement

iBattery 3.0
User Manual
Table 5-1 Setting iBOX parameters
Parameters
iBOX single
battery qty.
Batt installation
time
Battery string
capacity
Current source
Battery string No.
BCB tripping upon
battery abnormal
----End
5.4 Setting Parameters for the Scenario Where the iBOX
Connects to the NetEco
Procedure
Step 1 Set iBOX parameters.
1.
Issue 07 (2019-12-30)
Description
Total number of batteries monitored
by the iBOX.
Actual time at which batteries are
installed.
Capacity of a single battery
multiplied by the number of battery
strings.
Select a Hall effect sensor (xxx A).
The actual specifications of the Hall
effect sensor will apply.
The serial number of each battery
string. Set this parameter based on
the planned codes for iBOXs and
battery strings. The Battery string
No. are unique for a same UPS.
If the BCB box is configured, set
BCB tripping upon battery
abnormal to Enable.
If multiple iBOXs are connected, commission the iBOX one by one in the same way. Otherwise,
networking may be in disorder.
On the iBOX WebUI, choose System Settings > Batt. String Config, and set Batt.
String Config.
Copyright © Huawei Technologies Co., Ltd.
5 System Commissioning
Remarks
Set according to the battery
parameters planned by the
customer.
N/A
Obtain the battery capacity
from the battery label or
document.
The actual specifications of
the Hall effect sensor prevail.
Set according to the
customer plan.
N/A
51