Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 83

Master module
Table of Contents

Advertisement

Error code
Error details and causes
0D2CH
Slave module hardware error
0D2DH
Slave module hardware error
0D2EH
Parameter access target module ID
error
0D2FH
Parameter value error
0D30H
Parameter access error
0D31H
Slave module status error
0D80H
Type mismatch error
0D81H
Replacement error due to use of
slave module of earlier device version
0D83H
Non-compatible slave module
connection error detected in
compatibility inspection
Action
Writing data to read only areas in the slave module was
attempted.
Perform either of the following operations.
• Reset the CPU module or power off and on the system.
• Power off and on the slave module.
Check that there is no influence from noise.
When the error occurs during easy replacement for one slave
module or remote address change, check that the slave module
supports those functions.
Reading data from write only areas in the slave module was
attempted.
Perform either of the following operations.
• Reset the CPU module or power off and on the system.
• Power off and on the slave module.
Check that there is no influence from noise.
The RJ51AW12AL accessed the parameter of the ID where the
automatic address detection has not been executed.
Check that the slave module ID for parameter access in the
actual system matches that of the program.
• Bit input slave module ID (address + 200H)
• Bit I/O combined slave module ID (address + 200H)
• Word output slave module ID (address + 400H)
• Word input slave module ID (address + 600H)
• Word I/O combined slave module ID (address + 600H)
When creating a new system, adding or removing a slave
module, or changing the address of the slave module, execute
the automatic address detection. After executing the automatic
address detection function, check that the number of slave
modules and the address are consistent with those of the actual
system.
Check that one or more slave modules have been registered.
The slave module has detected a signal of writing a parameter
that cannot be set to the slave module itself.
Check 'Number of the alarm IDs' (Un\G9984) and 'Alarm ID
information storage area' (Un\G9985 to Un\G10112) to find out
the error ID. Then check that the slave module parameter
setting value is within the allowable setting range.
The parameter access signal sent by the RJ51AW12AL is
corrupt.
Check that none of the following errors have occurred. (
Page 29 How to check the parameter access error status)
• Slave module hardware error
• Slave module status error
• Same ID used error
When none of the above have occurred, check that there is no
influence from noise.
The slave module has notified of error status. Check the target
module's status details and solve the problem.
When a slave module is replaced using the easy replacement
function for one slave module, the type of the new slave module
is different from that of the old slave module.
Connect a proper slave module.
Replacement by the easy one-device replacement function has
failed because the old slave module was replaced with a new
slave module of an earlier device version than the one of the old
slave module.
For easy one-device replacement, replace the old slave module
with a new slave module of the same or a later device version
than the one of the old slave module.
During the AnyWireASLINK version compatibility inspection, a
non-compatible slave module was detected.
Refer to the manual of the slave module having the ID detected
in 'Sub information area' (Un\G12097 to Un\G12224).
Detailed information
4 TROUBLESHOOTING
4.4 List of Error Codes
4
81

Advertisement