Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 81

Master module
Table of Contents

Advertisement

When the AnyWireASLINK version compatibility inspection cannot be executed
When the AnyWireASLINK version compatibility inspection cannot be executed, check the following.
Check item
Is the word data points setting of the RJ51AW12AL valid?
Is an error code other than an AnyWireASLINK version compatibility
inspection error stored in the latest error code storage area?
Is a slave module with a duplicate ID connected?
Is a connected slave module broken?
Are slave modules more than the maximum number of connectable modules
connected?
When the backup/restoring function is not available
When the backup/restoring function is not available, check the following.
Check item
Is the CPU module in use support backup/restoration?
Action
Set the word data points setting of the RJ51AW12AL to 2 words (1 input word/
1 output word) or larger, and execute the AnyWireASLINK version
compatibility inspection.
Eliminate errors other than an AnyWireASLINK version compatibility
inspection error, and execute the AnyWireASLINK version compatibility
inspection.
Change the address of the slave module so that the ID is not duplicated, and
execute the AnyWireASLINK version compatibility inspection.
Replace the broken slave module, and execute the AnyWireASLINK version
compatibility inspection.
Reduce the number of connected slave modules to the maximum number of
connectable modules or less, and execute the AnyWireASLINK version
compatibility inspection.
Action
Use a CPU module that supports backup/restoration. For the versions of CPU
modules supporting backup/restoration, refer to the following.
 iQ Sensor Solution Reference Manual
4.3 Troubleshooting by Symptom
4 TROUBLESHOOTING
4
79