• A slave module address is not deleted even when the power supply of a programmable controller or a 24VDC external
power supply is turned off. The address is retained until a new address is set when a system is configured.
• In the address setting, ensure that the address occupied by the slave module does not exceed the number of transmission
points set in the RJ51AW12AL. For the operation mode setting of the RJ51AW12AL, refer to the following.
Page 49 Bit data setting
Ex.
When "Transmission points setting" is set to "0: 64 points (32 input points/32 output points)", the effective address range is
between 0 and 31.
If the address is set to 32 or larger, the slave module does not communicate I/O data.
When "Word data points setting" is set to "4: 8 words (input 4 words, output 4 words)", the effective address range is between
0 and 3.
If the address is set to 4 or larger, the slave module does not communicate I/O data.
• Do not use the following values when writing the address of the slave module. Doing so will cause a No ID setting error.
Model
Bit slave module
Word slave module
Address
255, 511
511