Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 105

Master module
Table of Contents

Advertisement

Alarm ID information storage area
■Alarm ID information storage area (Un\G9985 to Un\G10112)
This buffer memory area stores the ID information of all the slave modules where an alarm has occurred in the ascending
order.
The IDs to be stored are as follows.
• 0000H to 00FEH: ID of a bit output slave module
• 0200H to 02FEH: ID of a bit input slave module or bit I/O combined slave module
• 0400H to 05FEH: ID of a word output slave module
• 0600H to 07FEH: ID of a word input slave module or word I/O combined slave module
• 00FFH: Unset IDs of bit output slave modules and word output slave modules
• 02FFH: Unset IDs of bit input slave modules and word input slave modules
The stored values are retained until the power is turned off and on or 'Error flag clear command' (Y0) is turned off and on after
the error is cleared.
Data update timing
The data are updated when the power is turned on or when an alarm has occurred after automatic address detection.
Latest error code storage area
■Latest error code storage area (Un\G10256)
This buffer memory area stores the latest error code detected in the RJ51AW12AL. For details on the error codes, refer to the
following.
Page 80 List of Error Codes
Latest error ID storage area
■Latest error ID storage area (Un\G10257)
This buffer memory area stores the IDs corresponding to the error codes stored in 'Latest error code storage area'
(Un\G10256).
However, for the errors below, "0FFFH" is stored.
Error code
0CC8H
0CC9H
0CCBH
0D2EH
0D83H
0D84H
0D85H
0D92H
1867H
186EH
3064H to 3066H
3068H
3069H
306BH
306CH
Error description
Transmission cable voltage drop error
DP/DN short error
24V/DP short error
Parameter access target module ID error
Non-compatible slave module connection error detected in compatibility
inspection
Access error detected in compatibility inspection
Excessive number of connected slave modules error detected in compatibility
inspection
New ID error
EEPROM access error
EEPROM error (ID, parameter information)
RJ51AW12AL hardware failure
CPU module stop error (IORSTL signal detection)
System error (NMI signal detection)
CPU module error (ITERR signal detection)
ASIC access error (library I/F function access error)
APPX
Appendix 3 Buffer Memory
A
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r seriesMelsec iq anywireaslink rj51aw12al

Table of Contents