Precautions
■Conditions for performing the AnyWireASLINK version compatibility inspection
All the following conditions must be met to perform the AnyWireASLINK version compatibility inspection.
• The number of word data points is set to 2 words (1 input word/1 output word) or more.
• No errors exists on the RJ51AW12AL.
• 'Adjustment mode executing flag' (XF) is off.
• 'Parameter access completion flag' (X11) is on.
• 'Automatic address detection flag' (X14), 'Overlap address inspection flag' (X15), and 'One slave module changing flag'
(X16) are off.
Timing of the AnyWireASLINK version compatibility inspection
The following shows the timing of each step in the AnyWireASLINK version compatibility inspection.
■When the inspection is executed by 'AnyWireASLINK version compatibility inspection
command' (YD)
'AnyWireASLINK version compatibility
inspection command' (YD)
'AnyWireASLINK version compatibility
inspection executing flag' (XD)
'Parameter access completion flag' (X11)
LINK LED
ALM LED
Inputting/outputting word data or
bit data
'AnyWireASLINK version compatibility
inspection error' (X8)
(1) When 'AnyWireASLINK version compatibility inspection command' (YD) is turned off and on, 'AnyWireASLINK version compatibility inspection executing
flag' (XD) turns off and on, and 'Parameter access completion flag' (X11) turns on and off.
(2) The AnyWireASLINK version compatibility inspection starts.
(3) Parameter access is in progress.
(4) 'Parameter access completion flag' (X11) turns off and on upon completion of the parameter access.
(5) The AnyWireASLINK version compatibility inspection completes.
(6) When 'AnyWireASLINK version compatibility inspection command' (YD) is turned on and off, 'AnyWireASLINK version compatibility inspection executing
flag' (XD) turns on and off.
1 FUNCTIONS
46
1.15 AnyWireASLINK Version Compatibility Inspection Function
ON
(1)
OFF
ON
OFF
OFF
Flashing
Inputting/
outputting
OFF
(2)
(3)
On
Off
Stopping
(5)
(6)
(4)
ON
Flashing
On (error completion only)
Inputting/outputting
ON (error completion only)