Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual page 29

Master module
Table of Contents

Advertisement

How to recover from the transmission cable disconnection status
How to recover from the transmission cable disconnection status is as follows.
1.
Eliminate the disconnection in the AnyWireASLINK system.
When the disconnection status is exited, the AnyWireASLINK transmission resumes automatically.
When the slave module has been disconnected from the system, execute automatic address detection. ( Page 58
Automatic Address Detection Function)
2.
Power off and on the AnyWireASLINK system or turn on and off 'Error flag clear command' (Y0).
The following status is resulted:
• 'DP/DN disconnection error' (X4) turns off.
• The ALM LED turns off.
• The data in 'Latest error code storage area' (Un\G10256) and 'Latest error ID storage area' (Un\G10257) are cleared.
• When the automatic address detection is executed in the step 1, the operation in the step 2 is not
necessary.
• When the error status automatic recovery mode is enabled by "Error status automatic recovery" of "Basic
setting", the error is automatically cleared after the disconnection status is exited.
1.7 Disconnected Transmission Cable Location Detection Function