How to check the no ID number setting status
When the AnyWireASLINK system is in the following status, no ID number setting status is detected.
Even in the no ID number setting status, the AnyWireASLINK transmission does not stop.
• 'Slave module alarm signal' (X10) turns on.
• No ID setting error (error code: 0D91H) is stored in 'Latest error code storage area' (Un\G10256) and unset IDs are stored
in 'Latest error ID storage area' (Un\G10257).
• An error (error code: 0D91H) is displayed on an engineering tool. ( Page 75 Checking with the "Module Diagnostics"
*1
window)
• Unset IDs are stored in 'Alarm ID information storage area' (Un\G9985 to Un\G10112).
*1 If multiple errors occur simultaneously, the latest error is displayed.
How to recover from the no ID number setting status
Check 'Number of the alarm IDs' (Un\G9984) and 'Alarm ID information storage area' (Un\G9985 to Un\G10112). Then set
addresses to slave modules. ( Page 102 Number of the alarm IDs, Page 103 Alarm ID information storage area)
Check that the following address is not set as the address of the slave module.
Model
Bit slave module
Word slave module
Set IDs (addresses) of slave modules and execute automatic address detection of the RJ51AW12AL. Then, the IDs of the
slave modules are stored in the RJ51AW12AL and the error is cleared. ( Page 58 Automatic Address Detection Function)
For operations of slave modules with no ID assigned (default ID), refer to the following.
 Manual of the slave module used (manufactured by Anywire Corporation)
Precautions
While an ID (address) of a slave module is not set, executing either of the following can eliminate the no ID setting error.
However the address of the slave module is still not set.
• Powering off and on the AnyWireASLINK system
• Turning off and on 'Error flag clear command' (Y0)
1 FUNCTIONS
24
1.5 Module with No ID Setting Detection Function
*1
Address
255, 511
511