Anywireaslink Version Compatibility Inspection Function - Mitsubishi Electric MELSEC iQ-R AnyWireASLINK User Manual

Master module
Table of Contents

Advertisement

1.15
AnyWireASLINK Version Compatibility Inspection
Function
This function checks whether slave modules not supporting word data are connected to the RJ51AW12AL or not.
When using this function, check the production information of the RJ51AW12AL. ( Page 133 Added or
Changed Functions)
Operating procedure
1.
Perform either of the following operations.
• Turn off and on 'AnyWireASLINK version compatibility inspection command' (YD).
• While holding down the SET switch on the RJ51AW12AL, reset the CPU module or power off and on the system.
2.
The status will be changed as follows, and the AnyWireASLINK version compatibility inspection will start.
• 'AnyWireASLINK version compatibility inspection executing flag' (XD) turns off and on.
• 'Parameter access completion flag' (X11) turns on and off.
• The LINK LED stops flashing and stays on.
3.
When the AnyWireASLINK version compatibility inspection completes, the LINK LED stops illuminating and flashes.
(The inspection takes approximately 15 seconds.)
• The AnyWireASLINK transmission stops when the AnyWireASLINK version compatibility inspection starts.
• Error flags are cleared before the AnyWireASLINK version compatibility inspection starts. (As with turning
off and on 'Error flag clear command' (Y0))
How to check the error status
If an AnyWireASLINK version compatibility inspection error exists after the inspection, the status will be as follows.
Item
'AnyWireASLINK version compatibility inspection error' (X8)
'Latest error code storage area' (Un\G10256)
'Latest error ID storage area' (Un\G10257)
'Event code for sub information area' (Un\G12096)
'Sub information area' (Un\G12097 to Un\G12224)
ALM LED
The following are the probable causes of the AnyWireASLINK version compatibility inspection error. Identify the error cause
and take appropriate actions.
• The number of connected slave modules exceeds the limit.
• Parameter access fails on one or more slave modules.
• A slave module not supporting word data is connected to the RJ51AW12AL.
Clear the AnyWireASLINK version compatibility inspection error, and start the inspection again.
Description
Turns off and on.
The relevant error code is stored.
0FFFH is stored.
The relevant event code is stored.
The bits corresponding to target IDs of slave modules having an error are
turned on.
Turns on.