16.2.10 Writing commands

Writes a sequence program to the FX PLC. (Overwrite/Insert)
■1. Writing basic commands
(1) Operations
(a)
Inputting command only (Ex.: ANB, ORB command etc.)
Stop the FX PLC
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
(b)
Inputting command and device (LD, AND commands etc.)
Stop the FX PLC
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
Input the device name and device number
(c)
Inputting command, No. 1 device, No. 2 device (MC, OUT (T, C) commands, etc.)
Stop the FX PLC
For overwriting: (WRITE mode)
For insertion: (INSERT mode)
SP
(2) Example
(a)
Writing ORB command
Stop the FX PLC
MODE
With
cursor to the position to
overwrite/insert the command.
Input the command
MODE
Input the command
MODE
Input the command
MODE
Input the device name and device number
POINT
POINT
POINT
Moving the cursor to the position to write the command
When starting to write a command, place the cursor on the command line (the line on which the
step number is displayed).
You cannot write a command with the cursor on an operand or set value line.
2 LDI
M
100
3 MOV
D
D
< READ >
Set the
WRITE or
< WRITE >
INSERT
mode
or
, move the
GO
GO
Input the device name and device number
GO
Command line (Place the cursor on this line.)
12
0
Operand, set value line (Cannot operate on this line.)
10
4 LDI
5 AND
6 NOP
7 NOP
ORB
4 LDI
5 AND
6 ORB
7 NOP
16.2 FX List Editor (GT2105-Q, GT2104-R only)
X
004
X
005
GO
X
004
X
005