6
68(110)
6.2.2

Control terminal signals

OPT-A1
Terminal
1
+10 Vref
2
AI1+
3
GND/AI1–
4
AI2+
5
GND/AI2–
24 Vout
6
(bidirectional)
7
GND
DIN1
8
9
DIN2
10
DIN3
11
CMA
12
24 Vout
(bidirectional)
13
GND
14
DIN4
15
DIN5
16
DIN6
17
CMB
18
AO1+
19
AO1–
20
DO1
Table 6-9. Control I/O terminal signals on basic I/O board OPT-A1
CABLING AND CONNECTIONS
Signal
Reference voltage
Analogue input,
voltage or current
Analogue input common
Analogue input,
voltage or current
Analogue input common
24V auxiliary voltage
I/O ground
Digital input 1
Digital input 2
Digital input 3
Digital input common A for
DIN1, DIN2 and DIN3.
24V auxiliary voltage
I/O ground
Digital input 4
Digital input 5
Digital input 6
Digital input common B for
DIN4, DIN5 and DIN6
Analogue signal (+output)
Analogue output common
Open collector output
Technical information
Maximum current 10 mA
Selection V or mA with jumper block X1
Default: 0– +10V (Ri = 200 kΩ)
(-10V.....+10V Joy-stick control, selected with a jumper)
0– 20mA (Ri = 250 Ω)
Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
Selection V or mA with jumper block X2
Default: 0– 20mA (Ri = 250 Ω)
0– +10V (Ri = 200 kΩ)
(-10V.....+10V Joy-stick control, selected with a jumper)
Differential input if not connected to ground;
Allows ±20V differential mode voltage to GND
±15%, maximum current 250mA (all boards total);150mA
(from single board); Can also be used as external power
backup for the control unit (and fieldbus)
Ground for reference and controls
R
= min. 5kΩ
i
18...30V = "1"
Must be connected to GND or 24V of I/O terminal or
to external 24V or GND
Selection with jumper block X3
Same as terminal #6
Same as terminal #7
R
= min. 5kΩ
i
18...30V = "1"
Must be connected to GND or 24V of I/O terminal or to
external 24V or GND
Selection with jumper block X3
Output signal range:
Current 0(4)–20mA, R
max 500Ω or
L
Voltage 0—10V, R
>1kΩ
L
Selection with jumper block X6
Maximum U
= 48VDC
in
Maximum current = 50 mA
(see page 71):
(see page 71):
(see page 71):
(see page 71):
(see page 71):