4.2.2
NX_6 – Mains voltage 525—690 V
High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min
All sizes are available as IP21/NEMA1 Sizes FR4 to FR10 are additionally available as IP54/NEMA12.
FR12 is available only as NXP.
Mains voltage 525-690 V, 50/60 Hz, 3~
Frequency
converter
Low
type
Rated
10%
continuous
overload
current I
current
L
(A)
(A)
NX 0004 6
4.5
5.0
NX 0005 6
5.5
6.1
NX 0007 6
7.5
8.3
NX 0010 6
10
11.0
NX 0013 6
13.5
14.9
NX 0018 6
18
19.8
NX 0022 6
22
24.2
NX 0027 6
27
29.7
NX 0034 6
34
37
NX 0041 6
41
45
NX 0052 6
52
57
NX 0062 6
62
68
NX 0080 6
80
88
NX 0100 6
100
110
NX 0125 6
125
138
NX 0144 6
144
158
NX 0170 6
170
187
NX 0208 6
208
229
NX 0261 6
261
287
NX 0325 6
325
358
NX 0385 6
385
424
NX 0416 6
416
458
NX 0460 6
460
506
NX 0502 6
502
552
NX 0590 6
590
649
NX 0650 6
650
715
NX 0750 6
750
825
NX 0820 6
820
902
Table 4-2. Power ratings and dimensions of NX, supply voltage 525—690V.
Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to
or less than the factory default.
Note: The rated currents for FR10 to FR12 are valid at an ambient temperature of 40°C (except for 0416 6, 0590 6
and 0820 6: rated currents valid at an ambient temperature of 35°C).
TECHNICAL DATA
Following continuous operation at rated output current, 150 % rated output current (IH)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated output
current (IH)
Following continuous operation at rated output current, 110% rated output current (IL)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated output
current (IL)
Loadability
High
Rated
50%
Max
continuous
overload
current
current I
current
I
H
S
(A)
(A)
3.2
4.8
6.4
4.5
6.8
9.0
5.5
8.3
11.0
7.5
11.3
15.0
10
15.0
20.0
13.5
20.3
27
18
27.0
36
22
33.0
44
27
41
54
34
51
68
41
62
82
52
78
104
62
93
124
80
120
160
100
150
200
125
188
213
144
216
245
170
255
289
208
312
375
261
392
470
325
488
585
325
488
585
385
578
693
460
690
828
502
753
904
590
885
1062
650
975
1170
650
975
1170
Motor shaft power
690V supply
575V supply
10%
50%
10%
overload
overload
overload
40°C
50°C
40°C
P(kW)
P(kW)
P(hp)
3
2.2
3.0
4
3
3.0
5.5
4
5.0
7.5
5.5
7.5
10
7.5
11
15
10
15
18.5
15
20
22
18.5
25
30
22
30
37.5
30
40
45
37.5
50
55
45
60
75
55
75
90
75
100
110
90
125
132
110
150
160
132
150
200
160
200
250
200
250
315
250
300
355
315
400
400
315
450
450
355
450
500
450
500
560
500
600
630
560
650
710
630
800
800
630
800
19(110)
Dimensions and
50%
Frame
weight
overload
WxHxD/kg
50°C
P(hp)
2.0
FR6
195x519x237/18,5
3.0
FR6
195x519x237/18,5
3.0
FR6
195x519x237/18,5
5.0
FR6
195x519x237/18,5
7.5
FR6
195x519x237/18,5
11
FR6
195x519x237/18,5
15
FR6
195x519x237/18,5
20
FR6
195x519x237/18,5
25
FR6
195x519x237/18,5
30
FR7
237x591x257/35
40
FR7
237x591x257/35
50
FR8
291x758x344/58
60
FR8
291x758x344/58
75
FR8
291x758x344/58
100
FR9
480x1150x362/146
125
FR9
480x1150x362/146
150
FR9
480x1150x362/146
150
FR9
480x1150x362/146
200
FR10
595x2018x602/340
250
FR10
595x2018x602/340
300
FR10
595x2018x602/340
300
FR10
595x2018x602/340
400
FR11
794x2018x602/400
450
FR11
794x2018x602/400
500
FR11
794x2018x602/470
600
FR12
1210x2017x602/600
650
FR12
1210x2017x602/600
650
FR12
1210x2017x602/600
4