100(110)
Number of retries to receive HMI acknowledgement (P6.7.4)
With this parameter you can set the number of times the drive will try receive acknowledgement if this does
not succeed within the acknowledgement time (P6.7.3) or if the received acknowledgement is faulty.
Enter the edit mode by pushing the
Browser buttons
to change the amount of retries. Accept the change with the
previous level with the
See Figure 7-23 for the procedure of changing the value.
7.3.6.8

System info

In the System info submenu (S6.8) you can find frequency converter-related hardware and software
information as well as operation-related information.
Total counters (S6.8.1)
In the Total counters page (S6.8.1) you can find information related to the frequency converter operation
times, i.e. the total numbers of MWh, operation days and operation hours passed so far. Unlike the
counters in the Trip counters , these counters cannot be reset.
Note! The Power On time counter (days and hours) runs always, when the power is on.
Page
C6.8.1.1.
MWh counter
C6.8.1.2.
Power On day counter
C6.8.1.3.
Power On hour counter
Table 7-7. Counter pages
Trip counters (S6.8.2)
Trip counters (menu S6.8.2) are counters the values of which can be reset i.e. restored to zero. You have
the following resettable counters at your disposal. See Table 7-7 for examples.
Note! The trip counters run only when the motor is running.
Page
T6.8.2.1
MWh counter
T6.8.2.3
Operation day counter
T6.8.2.4
Operation hour counter
Table 7-8. Resettable counters
The counters can be reset on pages 6.8.2.2 (Clear MWh counter) and 6.8.2.5 (Clear Operation time
counter).
Example: When you want to reset the operation counters you should do the following:
CONTROL KEYPAD
Menu button
Menu button
left.
Counter
Value on display is 1.013. The drive has
operated for 1 year and 13 days.
Value on display is 7:05:16. The drive has
operated for 7 hours 5 minutes and 16 seconds.
Counter
right. The present value shown starts to blink. Use the
Example
Enter button
or return to the

Hide quick links: